Analysis Oil Condition of Transformer PT-8801-A by Using the Method TDCG, Rogers Ratio, Key Gas, and Duval Triangle: A Case Study at PT. Perta Arun Gas

Rastra Furqaranda, Andik Bintoro, Asri Asri, Waleed Khalid Ahmed Al-Ani, Ashish Shrestha

Abstract


The power transformer would have happened disturbanced that can cause a failure at a transformer. For this condition needed to maintenance power transformer, one of which is by analyzing transformer oil by using the TDCG method. This analysis is carried out to determine the diagnosis of faults in the transformer. This method are the condition of the analysis which is based on the amount of a gas dissolved on oil a transformer. This study used four methods for transformer failure analysis are TDCG method, Rogers-ratio, gas key, and duval triangle. The results obtained by the TDCG method of dissolved   gas are 1332 ppm, the roger’s ratio result a symptom of oil heat a transformer at 300oC, the key gas method results in overheating of oil, and the duval triangle method results in a low breakdown voltage analysis.


Keywords


power transformer, transformer oil, analysis method

Full Text:

PDF

References


Abu-Siada, A., & Islam, S. (2012). A new approach to identify power transformer criticality and asset management decision based on dissolved gas-in-oil analysis. IEEE Transactions on Dielectrics and Electrical Insulation, 19(3), 1007–1012.

Gouda, O. E., Saleh, S. M., & El-Hoshy, S. H. (2016). Power transformer incipient faults diagnosis based on dissolved gas analysis. Indonesian Journal of Electrical Engineering and Computer Science, 1(1), 10–16.

Ismail, R., Hasibuan, A., Nasution, E. S., Hardi, S., & Nrartha, I. M. A. (2020). Comparative analysis of differential relay settings in Langsa substation transformer to avoid protection failure. 2020 4rd International Conference on Electrical, Telecommunication and Computer Engineering (ELTICOM), 52–56.

KRISNA, J., & Bayusari, I. (2019). Perbandingan Metode Roger’s Ratio Dan Metode Duval’s Triangle Terhadap Kegagalan Transformator Dengan Pengujian Dga Pada Gardu Induk Di Sumatera Selatan. Sriwijaya University.

Manjang, S., Kitta, I., & Ikhlas, A. (2019). Voltage breakdown characteristics of transformer mineral oil with varies the composition of corn oil. 2019 2nd International Conference on High Voltage Engineering and Power Systems (ICHVEPS), 1–4.

Musil, R., Baur, M., & Pfister, W. (1995). Testing practices for the AC breakdown voltage testing of insulation liquids. IEEE Electrical Insulation Magazine, 11(1), 21–26.

Muttaqin, I., Hermawan, H., & Syakur, A. (2016). Analisis Pengaruh Pembebanan Dan Usia Pakai Terhadap Karakteristik Dan Estimasi Litefime Minyak Isolasi Transformator. Transient: Jurnal Ilmiah Teknik Elektro, 4(4), 1064–1071.

Nisworo, S., Hasibuan, A., & Daud, M. (2022). Evaluasi Kondisi Belitan Generator Transformers (GT) Dengan Sweep Frequency Response Analysis. RELE (Rekayasa Elektrikal Dan Energi): Jurnal Teknik Elektro, 5(1), 51–56.

Rahardjo, I. A., Subekti, M., Wahyudi, I., & others. (2021). Evaluation of Primary Distribution Disturbances Based on Causes of Failure at UP3 Menteng PT. PLN UID Jakarta Raya. Journal of Physics: Conference Series, 1737(1), 12006.

Rozga, P., Jayasree, T., Rao, U. M., Fofana, I., & Picher, P. (2021). Prebreakdown and Breakdown Phenomena in Ester Dielectric Liquids. Alternative Liquid Dielectrics for High Voltage Transformer Insulation Systems: Performance Analysis and Applications, 147–183.




DOI: https://doi.org/10.29103/jreece.v2i2.8567

Article Metrics

 Abstract Views : 296 times
 PDF Downloaded : 108 times

Refbacks

  • There are currently no refbacks.


Copyright (c) 2022 Rastra Furqaranda, Andik Bintoro, Asri, Waleed Khalid Ahmed Al-Ani, Ashish Shrestha

Creative Commons License
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.