Effects of Butylated Hydroxytoluene and Butylated Hydroxyanisole on Viscosity and Breakdown Voltage of Palm Oil

Authors

  • Yenni Afrida Universitas Lampung
  • Herman H Sinaga Universitas Lampung
  • Dewi A. Iryani Universitas Lampung
  • Nining Purwasih Universitas Lampung
  • Diah Permata Universitas Lampung

DOI:

https://doi.org/10.29103/jreece.v6i1.26366

Keywords:

Palm Oil, Antioxidant, Viscosity, Penetrating Voltage

Abstract

In the electric power system, insulating oil plays a pivotal role in separating two or more electrical conductors with different voltages. This separation is crucial to prevent unintended electrical connections or sparks that could compromise the system's safety and integrity. Mineral-based insulating oil is disadvantageous because it is classified as a mineral oil. This classification indicates that the waste is non-biodegradable, meaning biological processes cannot break it down. This characteristic can hurt the environment. Therefore, alternative efforts must be made to use liquid insulation, such as environmentally friendly vegetable oils. Vegetable oils are unsuitable as insulating oils due to their high viscosity, low oxidation stability, and good lubricity. A proposed solution to reduce palm oil viscosity involves adding additives. The dilution process can be enhanced by incorporating various additives, including butylated hydroxytoluene and butylated hydroxyanisole. The present study utilizes the Megger OTS80Af to assess the breakdown voltage and viscosity of the subject material. Vegetable oils are unsuitable as insulating oils due to their high viscosity, low oxidation stability, and good lubricity. A proposed solution to reduce palm oil viscosity involves adding additives. The dilution process can be enhanced by incorporating various additives, including butylated hydroxytoluene and butylated hydroxyanisole. The present study utilizes the Megger OTS80Af to assess the breakdown voltage and viscosity of the subject material. The experimental findings indicate that crude palm oil, when augmented with butylated hydroxytoluene and butylated hydroxyanisole, is deemed unsuitable for utilization as a transformer insulation medium. This determination is predicated on its inability to comply with the stipulated criteria outlined in SPLN 49-91: 1982, specifically the minimum breakdown voltage of 30 kV/2.5 mm for transformer insulation oil.

References

Ahmad, F., Khan, A. A., Khan, Q., & Hussain, M. R. (2019). State-of-art in nano-based dielectric oil: A review. IEEE Access, 7, 13396–13410.

Boufitra, I. (2023). Natural Butylated Hydroxytoluene (BHT): A Review. Quantum Journal of Medical and Health Sciences, 2(5), 1–13.

Chronis, I., Kalogeropoulou, S., & Psomopoulos, C. S. (2021). A review on the requirements for environmentally friendly insulating oils used in high-voltage equipment under the eco design framework. Environmental Science and Pollution Research, 28(26), 33828–33836.

Dai, S., Yu, C., Liang, M., Cheng, H., Li, W., Lai, F., Ma, L., & Liu, X. (2023). Oxidation characteristics and thermal stability of Butylated hydroxytoluene. Arabian Journal of Chemistry, 16(8), 104932.

Daud, M., Zulfikar, M. Y., Hasibuan, A., & Isa, M. (2023). Prototype of Automatic Watering and Fertilizing System for Oil Palm Seeds Based on Internet of Things. Andalas Journal of Electrical and Electronic Engineering Technology, 3(1), 1–9.

David, E., & Kopac, J. (2023). Survey on antioxidants used as additives to improve biodiesel’s stability to degradation through oxidation. Molecules, 28(23), 7765.

El-Harbawi, M. (2022). Fire and explosion risks and consequences in electrical substations—A transformer case study. ASME Open Journal of Engineering, 1.

Fitria, N., Hasibuan, A., Zulnazri, Z., Azhari, A., Safitri, N., & Ula, M. (2024). Techno-Economic Assessment of the Development of a Biogas Power Plant Made from Liquid Palm Oil Waste in Rantau Sub-District. Construction Technologies and Architecture, 14, 73–77.

Hasibuan, A., Isa, M., Siregar, W. V., & Nrartha, I. M. A. (2019). Sumber Bahan Bakar Dari Limbah Padat Pada Pembangkit Listrik Di Pabrik Kelapa Sawit. Ready Star, 2(1), 187–193.

Hemalatha, N., Kamaraja, A. S., Bhuvanesh, A., & Karthik Kumar, K. (2024). Analysis on insulating characteristics of natural high oleic ester and mineral oil based blended oil under accelerated thermal aging exposure. Biomass Conversion and Biorefinery, 14(23), 30383–30400.

Hemalatha, N., Kamaraja, A. S., Bhuvanesh, A., & Karthik Kumar, K. (2025). Exploring the insulating characteristics of transesterified used cooking oil and blends with corn oil infused with natural antioxidants. Biomass Conversion and Biorefinery, 15(3), 3385–3400.

Ismail, R., Hasibuan, A., Nasution, E. S., Hardi, S., & Nrartha, I. M. A. (2020). Comparative analysis of differential relay settings in Langsa substation transformer to avoid protection failure. 2020 4rd International Conference on Electrical, Telecommunication and Computer Engineering (ELTICOM), 52–56.

Maharani, C. P., Nrartha, I. M. A., Nugroho, S. I., & Hasibuan, A. (2024). Pengujian Tegangan Tembus Minyak Trafo pada Bay Trafo 1 di GI 150 kV Tanjung. Jurnal Informatika Dan Teknik Elektro Terapan, 12(3).

Mazzaro, M., De Bartolomeo, D., Bemporad, E., Berardi, S., Ledda, A., Calcara, L., Pompili, M., Falconi, M., Vecchio, A., Scatiggio, F., & others. (2017). Power transformer fire and environmental risk reduction by using natural esters. 2017 IEEE 19th International Conference on Dielectric Liquids (ICDL), 1–4.

Nisworo, S., Hasibuan, A., Daud, M., Studi, P., Elektro, T., Teknik, F., & Malikussaleh, U. (2022). Evaluasi Kondisi Belitan Generator Transformers (GT) Dengan Sweep Frequency Response Analysis. RELE (Rekayasa Elektrikal Dan Energi) : Jurnal Teknik Elektro, 5(1). https://doi.org/10.30596/rele.v5i1.10790

Nisworo, S., Hasibuan, A., Isa, M., Nrartha, I. M. A., & Jannah, M. (2024). Assessing transformer health through analysis of dissolved gases in cooling oil. International Journal of Applied, 13(4), 1014–1020.

Prastia, R., Asran, A., Hasibuan, A., Rosdiana, R., & Ezwarsyah, E. (2024). Analysis of Voltage Drop Improvement Using Transformer Insertion Method in LG-02 Receiver Lhokseumawe City. Applied Engineering, Innovation, and Technology, 1(1), 47–58.

Raj, R. A., Samikannu, R., Yahya, A., & Mosalaosi, M. (2020). An overview of potential liquid insulation in power transformer. International Journal on Energy Conversion, 8(4), 126–140.

Rozga, P., Beroual, A., Przybylek, P., Jaroszewski, M., & Strzelecki, K. (2020). A review on synthetic ester liquids for transformer applications. Energies, 13(23), 6429.

Tlhabologo, B. A., Samikannu, R., & Mosalaosi, M. (2021). Alternative liquid dielectrics in power transformer insulation: a review. Indonesian Journal of Electrical Engineering and Computer Science, 23(3), 1761–1777.

Downloads

Published

31-03-2026

Issue

Section

Articles